| Customization: | Available |
|---|---|
| Task: | Adjust |
| Structure: | Closed-Loop |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency



Parameter | Specification |
Rated Voltage | 6kV ± 10% ~ 66kV ± 10% |
PCC Voltage | 6kV ± 10% ~ 500kV ± 10% |
Input Voltage | 0.9 ~ 1.1pu; LVRT 0pu (150ms), 0.2pu (625ms) |
System Frequency | 50Hz/60Hz, allows short-term fluctuation |
Output Capacity | ± 1Mvar ~ ± 200Mvar |
Compensation Current Resolution | 0.5A |
Response Time | Full response time < 5ms |
Power Loss | ≤ 0.8% |
Total Harmonic Current Distortion (THDi) | ≤ 3% (≥ 25%P) |
Power Supply Mode | Dual power supply |
Control Power | 380VAC, 220VAC or 220VDC |
Reactive Power Regulation Mode | Automatic continuous smooth regulation (Capacitive/Inductive) |
Communication Interface | Ethernet, RS485, CAN, High-speed Fiber Optic Interface |
Communication Protocol | MODBUS_RTU, Profibus, Power CDT91, IEC61850-103/104 |
Operation Mode | Constant Device Reactive Power, Constant PCC Reactive Power, Constant PCC Power Factor, Constant PCC Voltage, Load Compensation Mode |
Parallel Connection Mode | Multi-unit parallel network operation, Multi-bus comprehensive compensation, Multi-group FC integrated compensation control |
Protection Function | Bus over/under voltage, SVG overcurrent, drive fault, power cell overvoltage/overcurrent/overheating & comm. fault; Protection for input/output interfaces, system power abnormality, etc. |
Fault Handling | Redundant design, supports N-2 |
Cooling Method | Air Cooling / Water Cooling |
Protection Class | Indoor IP30, Outdoor IP54 |
Storage Temperature | -40°C ~ +70°C |
Operating Temperature | -40°C ~ +55°C |
Relative Humidity | Monthly average ≤ 90% (at 25°C), non-condensing |
Altitude | ≤ 5000m |
Seismic Intensity | Degree VIII |
Pollution Degree | Class IV |